Purpose   • Technical details   • Installation and service   • Documentation

INTERFACE CONVERTER RS232/RS232 ISOLATED

Interface converter RS232/RS232 isolating

Interface converter initiative       Interface converter initiative - M       Interface converter RS232/BELL202       Interface converter RS232/RS485       Interface converter RS232/RS232 insulating       Interface converter RS232/ML       Interface Converter Controller       Interface converter SH/RS232       Converter Bell 202/CURRENT 4 - 20 mA       Isolating RS232 hub       Interface converter USB/PLI       Interface converter USB/BEL202       Interface converter RS485/PLI       Interface converter RS232/PLI изолирующий       Adapter BELL202       Interface converter RS485/BELL202

PURPOSE
( full specifications are in the manual for the device )

1. RS232/RS232 isolating interface converter is designed for galvanic isolation of physical signals of the RS232 interface and is used to organize the exchange of digital information via the RS232 interface between industrial controllers and PC.
2. The converter provides galvanic power isolation. Insulation strength - 500 VAC, 50 Hz within 60 sec.

TECHNICAL DETAILS

1. Power supply of the RS232/RS232 isolation converter is carried out from service signals (DTR, RTS, TX) RS232 interfaces or from connected external 10 - 14 V DC power supplies instead of DTR signals.
- intrinsic current consumption of the converter - no more than 4 mA.
- maximum power consumption . . . . - no more than 0.15W
2. The converter provides robust conversion for baud rates up to 38,400 bps.
3. The transmission delay introduced by the signal converter is no more than 2 µs.
4. The converter has protection against short circuits on all interface outputs.
5. The overall dimensions of the transducer are no more than 85 x 35 x 55 mm.
6. The mass of the converter does not exceed - 0.1 kg.
7. Service life of RS232/RS232 interface converter . . . . . - 12 years.

INSTALLATION & SERVICE

1. RS232/RS232 interface converter is designed for operation outside hazardous areas indoors at ambient temperature from minus 40 to plus 60 °С.
2. Degree of protection against environmental actions marking IP30.
3. The company provides warranty service for the converter within 24 months and after-sales service during the entire service life.

DOCUMENTATION  (Manual)

Power supply of the RS232/RS232 isolation.